Load & Demand – Electrician Journeyman Exam Study Guide
Overview
This study guide covers the essential load and demand concepts tested on the Electrician Journeyman Exam, including NEC code requirements, load calculation procedures, and special load considerations. Mastery of these topics requires understanding both the underlying electrical theory and the specific NEC tables and percentages used in real-world calculations. Expect calculation-based questions that require you to apply demand factors, VA values, and sizing rules quickly and accurately.
---
Definitions & Core Concepts
Foundational Terms
Key Formula
```
Demand Load = Connected Load × Demand Factor
```
Demand Factor vs. Diversity Factor Compared
| Feature | Demand Factor | Diversity Factor |
|---|---|---|
| Formula | Max Demand ÷ Connected Load | Sum of Individual Demands ÷ System Max Demand |
| Value Range | ≤ 1 (≤ 100%) | ≥ 1 |
| Purpose | Reduces connected load | Accounts for staggered peak demands |
Key Terms
> Watch Out For: Students commonly confuse demand factor and diversity factor. Remember: demand factor goes DOWN (less than 1), diversity factor goes UP (greater than or equal to 1). They move in opposite directions.
---
NEC Code Requirements
General Lighting Loads – Dwelling Units
Unit Load: 3 VA per square foot for dwelling unit general lighting (NEC Table 220.12)
#### NEC Table 220.42 – Demand Factors for General Lighting (Dwelling Units)
| Portion of Lighting Load | Demand Factor |
|---|---|
| First 3,000 VA | 100% |
| 3,001 VA to 120,000 VA | 35% |
| Over 120,000 VA | 25% |
Required Branch Circuit Loads (Dwelling Units)
| Circuit Type | Required Quantity | VA Each |
|---|---|---|
| Small Appliance Branch Circuits | Minimum 2 | 1,500 VA |
| Laundry Branch Circuit | Minimum 1 | 1,500 VA |
> Watch Out For: Small appliance and laundry branch circuit VA allowances (1,500 VA each) are added to the general lighting load before demand factors are applied in the Standard Calculation Method. Don't forget these mandatory additions.
Continuous Load Conductor Sizing
Per NEC 210.19(A)(1):
Minimum Service Size
Key Terms
> Watch Out For: The 35% demand factor for general lighting applies to a very wide range (3,001–120,000 VA). On most residential calculations, nearly all of your lighting load above 3,000 VA will fall into this bracket.
---
Load Calculation Methods
Two Permitted Methods for Dwelling Unit Services
#### 1. Standard Calculation Method – NEC 220.82
#### 2. Optional Calculation Method – NEC 220.83
| Portion of "All Other Loads" | Demand Factor |
|---|---|
| First 10 kVA | 100% |
| All loads exceeding 10 kVA | 40% |
> The optional method is often simpler and may yield a smaller (more economical) calculated load for larger homes.
Step-by-Step: Standard Dwelling Calculation (Summary)
```
Step 1: Calculate general lighting load
= Square Footage × 3 VA/sq ft
Step 2: Add small appliance loads
= 2 circuits × 1,500 VA = 3,000 VA
Step 3: Add laundry circuit load
= 1,500 VA
Step 4: Apply Table 220.42 demand factors to Steps 1–3 total
Step 5: Add range load (Table 220.55)
1 range = 8,000 VA (8 kW) Column C
Step 6: Add dryer load (Table 220.54, min. 5,000 W)
Step 7: Add heating OR A/C (whichever is larger)
Step 8: Add largest motor at 125%
Step 9: Convert total VA to amperes
I = VA ÷ Volts
```
Worked Example: General Lighting
Given: 2,000 sq ft dwelling unit
```
Connected Lighting Load = 2,000 × 3 VA = 6,000 VA
+ Small appliance circuits = 3,000 VA
+ Laundry circuit = 1,500 VA
Total before demand = 10,500 VA
Apply Table 220.42:
First 3,000 VA × 100% = 3,000 VA
Remaining 7,500 VA × 35% = 2,625 VA
Demand Load Total = 5,625 VA
```
Worked Example: Service Ampere Rating
Given: 240V single-phase, 24,000 VA calculated demand load
```
I = VA ÷ V
I = 24,000 ÷ 240
I = 100 amperes → Minimum 100A service required
```
Key Terms
> Watch Out For: Don't use the "demand load" formula on ranges without checking Table 220.55. A single range defaults to 8 kW (8,000 VA) regardless of actual nameplate rating (for ranges rated 8¾ kW or less, use Column C values).
---
Motor & Special Loads
Motor Load Rule
Per NEC, when calculating feeder or service loads:
```
Largest Motor Contribution = FLC × 1.25
```
Electric Ranges – NEC Table 220.55
| Number of Ranges | Demand (Column C) |
|---|---|
| 1 range | 8,000 VA (8 kW) |
| Multiple ranges | See Table 220.55 for further reductions |
Electric Dryers – NEC Table 220.54
| Number of Dryers | Demand Factor |
|---|---|
| 1 | 100% |
| 2 | 100% |
| 3 | 100% |
| 4 | 100% |
| 5+ | Reductions begin |
Minimum dryer load: 5,000 W (5 kW) per dryer, or nameplate rating if higher.
> Watch Out For: Many students expect a demand reduction for 2 dryers — there is none. The 100% demand factor holds through the first several units. Reductions only apply to larger multifamily scenarios with 5+ dryers.
Fixed Electric Space Heating – NEC 220.51
Air Conditioning vs. Electric Heat – Omission Rule
Key Terms
> Watch Out For: The 125% motor rule applies only to the single largest motor on the feeder/service. Do not multiply all motors by 125% — only the largest one.
---
Quick Review Checklist
Use this checklist before your exam to confirm mastery of all key concepts:
---
Tip: Practice at least five full dwelling unit load calculations — one using the Standard Method and one using the Optional Method — before exam day. Speed and accuracy with these procedures is essential.