← Grounding & Bonding – Electrician Journeyman Exam

Electrician Journeyman Exam Study Guide

Key concepts, definitions, and exam tips organized by topic.

30 cards covered

Grounding & Bonding – Electrician Journeyman Exam Study Guide


Overview

Grounding and bonding are foundational safety concepts governed primarily by NEC Article 250. Grounding establishes a reference potential to earth, while bonding ensures electrical continuity across metallic components to safely carry fault currents. Together, they protect equipment and personnel by providing a reliable path for fault current to operate overcurrent devices.


---


Definitions & Core Concepts


Grounding vs. Bonding


| Concept | Definition | Purpose |

|---|---|---|

| Grounding | Intentional connection of a conductor to earth or conductive body serving in place of earth | Establishes reference potential |

| Bonding | Permanent joining of metallic parts to form an electrically conductive path | Ensures continuity; safely carries fault current |


Critical Conductor Distinctions


  • Grounded Conductor (Neutral)
  • - Intentionally connected to ground

    - Carries return current under normal operation

    - Must be white, gray, or three continuous white stripes (6 AWG and smaller)


  • Grounding Conductor / Equipment Grounding Conductor (EGC)
  • - Safety conductor — carries no current under normal conditions

    - Provides fault current return path to operate overcurrent devices

    - Must be green, green with yellow stripe(s), or bare


    > Watch Out For: Students frequently confuse the grounded conductor (neutral) with the grounding conductor (EGC). They serve entirely different functions. The neutral carries load current; the EGC does not — until a fault occurs.


    Key Bonding Devices


  • Main Bonding Jumper (MBJ): Connects the grounded (neutral) conductor to the EGC and grounding electrode conductor at service equipment. This completes the ground-fault current path.
  • System Bonding Jumper: Performs the same function as the MBJ but at a separately derived system (e.g., transformer secondary).
  • Equipment Bonding Jumper (EBJ): Connects two or more portions of the EGC system across connections that may not provide reliable conductivity on their own.

  • Separately Derived System


  • • A system with no direct electrical connection (including no solidly connected grounded circuit conductor) to the supply conductors of another system
  • • Common examples: isolation transformers, generators
  • • Requires its own system bonding jumper and grounding electrode

  • > Watch Out For: The system bonding jumper must be installed at either the source or the first disconnect — never both locations. Installing it at both creates parallel neutral paths and is a code violation (NEC 250.30(A)(1)).


    Key Terms

  • Grounding Electrode System – All grounding electrodes at a building bonded together into a single system (NEC Article 250)
  • Ground-Fault Current Path – The electrically conductive path from a ground fault back to the source, designed to facilitate overcurrent device operation
  • Separately Derived System – A premises wiring system with no direct electrical connection to the originating supply system

  • ---


    Grounding Electrode System


    Electrode Types and Requirements


    #### Ground Rod Electrodes

  • • Minimum 8 feet of rod must be in contact with soil (NEC 250.53(G))
  • • Steel or iron rods: minimum 5/8 inch diameter
  • • Copper-clad steel rods: minimum 1/2 inch diameter
  • • Must be driven to full depth; if rock prevents it, may be buried in a trench at 30° or less from vertical

  • #### Concrete-Encased Electrode (Ufer Ground)

  • • Encased in at least 2 inches of concrete
  • • Located within and near the bottom of a concrete foundation or footing in direct contact with earth
  • • Requires at least 20 feet of either:
  • - Steel rebar no less than 1/2 inch diameter, OR

    - Bare copper conductor 4 AWG or larger


    #### Metal Underground Water Pipe

  • • Acceptable electrode but must be supplemented by an additional electrode
  • • Not reliable as a sole electrode — water pipe continuity can be interrupted by maintenance
  • • A bonding jumper must bridge any water meter when the pipe serves as an electrode or bonding path (NEC 250.53(D)(1))

  • Supplemental Ground Rod Requirements

  • • If a single ground rod does not achieve 25 ohms or less resistance to ground, a second electrode must be added
  • • Supplemental rod must be spaced at least 6 feet from the first rod
  • • Greater spacing improves effectiveness (reduces mutual resistance)

  • > Watch Out For: You do NOT need to measure resistance if you simply install two rods from the start. The 25-ohm rule only triggers the requirement for a second rod when only one rod is initially installed.


    Key Terms

  • Ufer Ground – Concrete-encased electrode; often considered the most reliable electrode type
  • Grounding Electrode Conductor (GEC) – Conductor connecting the grounding electrode system to the service or separately derived system
  • 25-Ohm Rule – Resistance threshold that triggers the requirement for a supplemental ground rod (NEC 250.56)

  • ---


    Conductor Sizing


    Grounding Electrode Conductor (GEC) Sizing


  • • Sized per NEC Table 250.66 based on the largest service-entrance conductor
  • • Special caps apply for certain electrode types:

  • | Electrode Type | Maximum GEC Size Required |

    |---|---|

    | Single ground rod | 6 AWG copper (NEC 250.66(A)) |

    | Concrete-encased electrode | 4 AWG copper (NEC 250.66(B)) |

    | Ground ring | Same size as ring conductor (NEC 250.66(C)) |


    > Watch Out For: The caps above apply only to the portion of the GEC running to that specific electrode. The GEC from the service to the electrode system itself is still sized per Table 250.66 without a cap.


    Equipment Grounding Conductor (EGC) Sizing


    Sized per NEC Table 250.122 based on the overcurrent device protecting the circuit:


    | Overcurrent Device Rating | Minimum Copper EGC |

    |---|---|

    | 15 amp | 14 AWG |

    | 20 amp | 12 AWG |

    | 30 amp | 10 AWG |

    | 60 amp | 10 AWG |

    | 100 amp | 8 AWG |

    | 200 amp | 6 AWG |


    > Watch Out For: If ungrounded (hot) conductors are upsized for voltage drop or any other reason, the EGC must be proportionally increased based on circular mil area — not just bumped up one size (NEC 250.122(B)).


    Main Bonding Jumper & Bonding Jumper Sizing


  • • Sized per NEC Table 250.102(C)(1) based on the service-entrance conductor size
  • • Examples:

  • | Service-Entrance Conductor (Copper) | Minimum Bonding Jumper (Copper) |

    |---|---|

    | 2/0 AWG | 4 AWG |

    | 3/0 AWG | 2 AWG |

    | 4/0 AWG | 2 AWG |

    | 250 kcmil | 2 AWG |


    Key Terms

  • NEC Table 250.66 – GEC sizing table based on service conductor size
  • NEC Table 250.122 – EGC sizing table based on overcurrent device rating
  • NEC Table 250.102(C)(1) – Bonding jumper sizing table
  • Circular Mil Area – Unit used for proportional EGC upsizing calculations

  • ---


    Service & Equipment Grounding


    Service Equipment Rules


  • • Metal conduits containing service-entrance conductors must be bonded at each end using:
  • - Listed bonding locknuts

    - Bonding bushings

    - Other listed bonding fittings

    - (Standard locknuts alone are not acceptable at service equipment — NEC 250.92(B))


    Sub-Panel (Non-Service Panel) Rules


  • • The neutral bar and ground bar must be separate and isolated from each other
  • • The neutral must never be bonded to the enclosure in a sub-panel
  • • The MBJ is installed only at the service equipment — never downstream

  • > Watch Out For: This is one of the most common exam topics and field violations. Connecting neutral to ground (or to the enclosure) in a sub-panel creates objectionable current on grounding conductors and metallic enclosures — a serious shock hazard.


    Conductor Identification Requirements


    | Conductor | Required Identification |

    |---|---|

    | Grounded (Neutral) — 6 AWG and smaller | White or gray insulation, or three continuous white stripes |

    | Grounded (Neutral) — larger than 6 AWG | White, gray, or white/gray marking at terminations |

    | EGC (insulated) | Green, green with yellow stripe(s), or bare |


    Key Terms

  • Service Equipment – The necessary equipment, usually a circuit breaker or fused switch, located near the point of entrance of supply conductors
  • Listed Bonding Fitting – A fitting evaluated and listed specifically for bonding purposes at service equipment

  • ---


    Bonding Requirements


    Interior Metal Water Piping

  • • Must be bonded to the service equipment enclosure, GEC, grounding electrode, or grounded conductor at the service
  • • Bonding jumper sized per NEC Table 250.102(C)(1)

  • Metal Gas Piping

  • • Must be bonded to the EGC of the circuit that may energize it
  • • Bonding jumper sized per NEC Table 250.122 (NEC 250.104(B))

  • Structural Metal Framing

  • • Must be bonded to the service equipment enclosure, grounded conductor at the service, GEC, or grounding electrode when likely to become energized (NEC 250.104(C))

  • Water Meter Bonding Jumper

  • • Required whenever the metal water pipe is used as a grounding electrode or part of the bonding path
  • • Reason: Water meters are routinely removed for maintenance, which would break the grounding/bonding continuity

  • Service Conduit Bonding

  • • All metal raceways and enclosures containing service conductors must be bonded — standard locknuts are insufficient
  • • Must use listed bonding means at each end of the conduit

  • > Watch Out For: Regular locknuts are approved for general wiring methods but are not listed bonding fittings. At service equipment, you must use specific bonding locknuts, bonding bushings with bonding jumpers, or other listed means.


    Key Terms

  • Objectionable Current – Current flowing on grounding conductors or metallic enclosures under normal operation; a code violation and shock hazard
  • Bonding Jumper – A conductor used to ensure electrical continuity between metal parts
  • NEC 250.104 – Article covering bonding requirements for piping and structural metal

  • ---


    Quick Review Checklist


    Use this checklist to confirm mastery of the most critical exam topics:


  • • [ ] I can define grounding and bonding and explain why both are necessary
  • • [ ] I can distinguish between the grounded conductor (neutral) and the equipment grounding conductor (EGC)
  • • [ ] I know the MBJ connects neutral to EGC at service equipment only — never in a sub-panel
  • • [ ] I understand where the system bonding jumper is placed in a separately derived system (source OR first disconnect — not both)
  • • [ ] I know ground rods must have 8 feet in soil contact and steel rods must be 5/8 inch minimum diameter
  • • [ ] I know the 25-ohm rule requires a supplemental electrode spaced at least 6 feet from the first
  • • [ ] I can identify Ufer ground requirements: 2 inches of concrete, 20 feet of rebar (½ inch min.) or 4 AWG bare copper
  • • [ ] I can size the GEC using Table 250.66 and know the electrode-specific caps (6 AWG for single rod, 4 AWG for Ufer)
  • • [ ] I can size the EGC using Table 250.122 based on the overcurrent device rating
  • • [ ] I know EGCs must be proportionally upsized when conductors are increased for voltage drop (NEC 250.122(B))
  • • [ ] I can size bonding jumpers using Table 250.102(C)(1)
  • • [ ] I know neutral and ground must be isolated in any sub-panel (non-service equipment)
  • • [ ] I know standard locknuts are not acceptable for bonding service conduits — listed bonding fittings are required
  • • [ ] I know a bonding jumper must be installed around water meters when the pipe serves as an electrode
  • • [ ] I can identify EGC color codes: green, green/yellow stripe, or bare
  • • [ ] I can identify neutral color codes: white or gray (6 AWG and smaller)

  • ---


    Reference: NFPA 70 National Electrical Code (NEC), Article 250 — Grounding and Bonding

    Want more study tools?

    Subscribe for $7.99/mo and turn your own notes into personalized flashcards and study guides.

    View Pricing